Line and load reactors (3 phases)

Without reactors of line
With reactors of Polaris line
TDH = 147.9%
TDH = 35.4%
1566V AC (crête)
1026V AC (crête)
1025V AC 322Amps
1070V AC 71Amps

Return to the previous page

With reactor of  linePolaris
TDH = 35.4%


Amplitude of the harmonics of Drive, 100% of the nominal couple, 59 Hz, phase A.


Without reactor of line
TDH = 147.9%


Without reactor of line
1566V AC (crête)


Terminal voltage of the engine, without impedance.


With reactor of line Polaris
1026V AC (crête)


Terminal voltage of the engine, with impedance of 5% at the exit of drive.



Without reactor of line
1025V AC 322Amps


Response to the interlocking of the condensers, without impedance, 75 of the couple nomminal.


With reactor of  line Polaris
1070V AC 71Amps


With impedance of 3%, 75% of the couple nomminal.